 | The hose shall be of double jacket construction with 100% virgin spun polyester yarn in both jackets. |
 | There shall be a minimum of 10.0 filler yarns per inch in both the inner and outer jackets. |
 | The thickness of the lining shall be 0.015" (391 µm) minimum and it shall be constructed of extruded T.P.U. elastomer. |
 | The outside jacket shall be treated with green ENCAP™ elastomer, which shall completely encapsulate the jacket fibers and not merely surface coat the jacket. |
 | The hose service temperature range shall be -60°F to 150°F (-51°C to 66°C). |
 | FM abrasion test of 15,000 cycles minimum and Taber abrasion test of 5,000 cycles minimum. |
 | At 800 PSIG (5600 kPa), its elongation shall not exceed 10% of the initial hose length; it shall not warp more than 20 inches (51 cm) and should not rise from the test table. |
 | The hose shall not twist more than 2 1/2 turns per 50 ft (15,2 m) while at 800 PSIG (5600 kPa). |
 | Minimum service test pressure of 600 PSIG (4200 kPa). |
 | Minimum proof test pressure of 800 PSIG (5600 kPa). |
 | Minimum straight burst test pressure of 1800 PSIG (12600 kPa). |
 | The hose while curved to a radius of 27" (69 cm) shall not burst at less than 1600 PSIG (11200 kPa). |
 | Meets or exceeds NFPA 1961. |