STANDPIPE 600™

 Used to support standpipe systems of high-rise buildings that need greater pump pressures. STANDPIPE 600™ is a 100% polyester, 3" (76 mm) double jacket hose, lined with TPU elastomer. It has a service test pressure rating of 600 PSIG (4200 kPa) and is equipped with standard 2 1/2" (64 mm) NST couplings. STANDPIPE 600™ is green ENCAP™ treated for added durability and enhanced abrasion resistance. Specifically designed to meet the needs of fire departments faced with the challenges of pumping to high-rise buildings


 

  

  STANDPIPE 600™ specifications

 
bullet

The hose shall be of double jacket construction with 100% virgin spun polyester yarn in both jackets.

bullet

There shall be a minimum of 10.0 filler yarns per inch in both the inner and outer jackets.

bullet

The thickness of the lining shall be 0.015" (391 µm) minimum and it shall be constructed of extruded T.P.U. elastomer.

bullet

The outside jacket shall be treated with green ENCAP™ elastomer, which shall completely encapsulate the jacket fibers and not merely surface coat the jacket.

bullet

The hose service temperature range shall be -60°F to 150°F (-51°C to 66°C).

bullet

FM abrasion test of 15,000 cycles minimum and Taber abrasion test of 5,000 cycles minimum.

bullet

At 800 PSIG (5600 kPa), its elongation shall not exceed 10% of the initial hose length; it shall not warp more than 20 inches (51 cm) and should not rise from the test table.

bullet

The hose shall not twist more than 2 1/2 turns per 50 ft (15,2 m) while at 800 PSIG (5600 kPa).

bullet

Minimum service test pressure of 600 PSIG (4200 kPa).

bullet

Minimum proof test pressure of 800 PSIG (5600 kPa).

bullet

Minimum straight burst test pressure of 1800 PSIG (12600 kPa).

bullet

The hose while curved to a radius of 27" (69 cm) shall not burst at less than 1600 PSIG (11200 kPa).

bullet

Meets or exceeds NFPA 1961. 

 

 
Physical properties
Hose SizeSpec NumberCoupling bowl sizeWeight per 50 ftCoil Diameter per 50 ftMinimum Kink Burst Test Pressure
3"
(76 mm)
42303 1/2"
(88.9 mm)
38 lbs
(17.2 kg)
17"
(43 cm)
1600 PSIG
(11200 kPa)

 