 | The hose shall be a single jacket construction of 100% virgin spun polyester, red ENCAPTM treated, combined with a special helical interior reinforcement. |
 | There shall also be a minimum of 12.5 filler yarns per inch in the jacket. |
 | The thickness of the lining shall be 0.028" (711 µm) minimum and it shall be constructed of lightweight extruded T.P.U. elastomer. |
 | The outside jacket shall be treated with red ENCAPTM elastomer which shall completely encapsulate the jacket fibers and not merely surface coat the jacket. |
 | The hose service temperature range shall be -60°F to 140°F (-50°C to 60°C). |
 | The hose’s exterior can melt at 500°F (260°C) and burn at 550°F (287°C). |
 | FM abrasion test of 15,000 cycles minimum. |
 | At 600 PSIG (4200 kPa), its elongation shall not exceed 8% of the initial hose length, it shall not warp more than 20 inches (51 cm) and should not rise from the test table. |
 | The hose shall not twist more than 9 turns per 50 ft (15,2 m) while at 600 PSIG (4200 kPa). |
 | Minimum service test pressure of 300 PSIG (2100 kPa). |
 | Minimum proof test pressure of 600 PSIG (4200 kPa). |
 | Minimum straight burst test pressure of 1800 PSIG (12600 kPa). |
 | The hose while curved to a radius of 27" (69 cm) shall not burst at less than 1800 PSIG (12600 kPa). |
 | Meets or exceeds NFPA 1961 specifications. |