 | The hose shall be a single jacket construction with 100% spun polyester yarn. |
 | There shall be a minimum of 21.0 filler yarns per inch in the jacket. |
 | The thickness of the lining shall be 0.012" (305 µm) minimum and it shall be constructed of extruded T.P.U. elastomer. |
 | If required (optional), the outside jacket shall be treated with yellow ENCAP elastomer, which shall completely encapsulate the jacket fibers and not merely surface coat the jacket. |
 | The hose service temperature range shall be -60°F to 140°F (-51°C to 60°C). |
 | At 300 PSIG (2100 kPa), its elongation shall not exceed 2% of the initial hose length, it shall not warp more than 10 inches (25 cm) and should not rise from the test table. |
 | The hose shall not twist more than 5 turns per 50 ft (15,2 m) while at 300 PSIG (2100 kPa). |
 | Minimum service test pressure of 150 PSIG (1050 kPa). |
 | Minimum proof test pressure of 300 PSIG (2100 kPa). |
 | Minimum straight burst test pressure of 600 PSIG (4200 kPa). |
 | The hose while curved to a radius of 27" (69 cm) shall not burst at less than 600 PSIG (4200 kPa). |